Technical data

Performance characteristics conductivity
Conductivity                                         14 selectable ranges
Min. measurable conductivity                    50 µS/cm
Max. measuring span                              1000 mS/cm
Min. measuring span                               500 µS/cm
Max. measuring error                              ± 1.0 % FSR , 0 … 1 mS/cm to 0 … 500 mS/cm
                                                          ± 1.5 % FSR , 0 … 1000 mS/cm
                                                          ± 1.5 % FSR , 0 … 500 µS/cm
Reference temperature                            25 °C , adjustable
Repeatability                                          < 0.5 % FSR , > 1 mS/cm
Compensated temperature range              -20 … 150 °C
Temperature compensation                      0.0 … 5.0 % FSR/K , adjustable
Step response time, T90                          ≤ 2.0 s
Sample time                                          ≤ 0.4 s

Performance characteristics concentration
Concentration                                        Programmable with IO-Link and FlexProgram
Factory set media (available from FlexProgram)        0 … 25 % by weight , HNO3 (nitric acid)
                                                                      36 … 82 % by weight , HNO3 (nitric acid)
                                                                      0 12 % by weight , NaOH (caustic soda)
                                                                      25 50 % by weight , NaOH (caustic soda)
Customer defined media                                     Customer defined (30 point lookup table)

Performance characteristics temperature
Temperature                                            Free programmable range
Measuring range                                      -20 … 150 °C
Thermal response time, T90                       ≤ 15 s
Max. measuring error                                ± 1.5 K
                                                            0.3 K , 20 … 50 °C

Process conditions
Process temperature                                 -20 … 140 °C , permanent
                                                             140 … 150 °C , max. t < 1 h
Process pressure                                       ≤ 25 bar

Process connection
Connection variants                                  G 1 A hygienic
Wetted parts material                                PEEK Natura
Surface roughness wetted parts                  Ra ≤ 0.8 µm

HART® interface
Properties                                              Universal commands
                                                           Common-practice commands
                                                           Conductivity device family commands
                                                           Device Specific Commands
                                                           For more information please see ‚HART Field Device Specification‘
Protocol                                                HCF standard, Rev.7

IO-Link interface
IO-Link version                                      1.1
Device profile                                        Smart Sensor Profile
Baud rate                                             38,4 kbaud (COM2)
Cycle time                                            ≥ 8.4 ms
Process data length                               128 bit
SIO-mode                                             Yes
Process data (cyclic)                               Switch state
                                                          Signal analog output 1
                                                          Signal analog output 2
                                                          Temperature
                                                          Unit temperature
                                                          Conductivity
                                                          Concentration
                                                          Actual measuring range

Ambient conditions
Degree of protection (EN 60529)               IP67
                                                          IP69K , with appropriate cable

Compliance and approvals
EMC                                                     EN 61326-1
Hygiene                                                3-A (74-07)
                                                           EHEDG EL Class I
                                                           FDA (21 CFR 177.2415)
Safety                                                   cULus listed, E491206