คุณสมบัติสินค้า:

Programmable flow sensor

Flow sensors & Flow meters

หมวดหมู่ : Process sensors Flow sensors & Flow meters

Share

คุณสมบัติ

General information
Range of application                        Conductive liquid media (conductivity: >= 20 µS/cm / viscosity: < 70 mm²/s at 40°C)
Flow measuring range                      0.2 ... 50 l/min
Parametrisation options                     Hysteresis / window
                                                    Normally open / Normally closed
                                                    Switching logic
                                                    Display can be turned off
                                                    Current/ voltage /pulse output
                                                    Start-up suppression time
                                                    Display unit
Temperature measuring range min.      -20 °C
Temperature measuring range max.      80 °C

Outputs / inputs


Pulse output                                   Yes
Counter reset                                 Yes
Switching output                             2 x normally closed / normally open programmable
Analogue output                             4 ... 20 mA
                                                   0 ... 10 V
                                                   Programmable
                                                   Scalable
Comment on analogue output           When used with an analog output use exclusively sensor cables without LED
IO-Link                                         Yes

 
Electrical data


Operating voltage                          19 ... 30 V DC
Voltage type                                 Direct voltage (DC)
Electrical design                            PNP
                                                  NPN*
                                                 *Programming buttons
                                                 *IO-Link parameterisation
Current carrying capacity max.          2 x 200 mA
Voltage drop max.                          2 V
Current consumption max.               120 mA
Protection class                             III
Short-circuit protection                   Yes
Overload-proof                              Yes
Reverse polarity protection              Yes

Mechanical data


Materials in contact with the medium     V4A (1.4404)
                                                      FKM
                                                      PEEK
Material of housing                             V4A (1.4404)
                                                      FKM
                                                      PC
                                                      PBT-GF 20
Electrical connection                           M12
                                                      4-pin
                                                      Contacts gold-plated
Pressure resistance                             16 bar
Process connection                             Flat sealing
                                                      External thread
                                                      G 3/4

Accuracy


Resolution                                        0.1 l/min | 0.2 °C
Reproducibility                                  ± 0.2% MREV * (flow monitoring)
Response dynamics of T05 / T09         T09 = 20 s (temperature monitoring)
Comment                                        * MV = measured value, MREV = measurement range end value
Accuracy                                         ± (2 % MV + 0.5 % MREV * | ± 2.5 °C
Ready delay                                     5 s
Response time                                 0.15 s (flow monitoring

Ambient conditions


Ambient temperature min.                 -10 °C
Ambient temperature max.                 60 °C
Protection rating                              IP67